Issue
An APC Network Management Card must be configured with network settings before it can communicate on the network. Once the cards have been configured with an IP address, Subnet Mask, and Default Gateway the cards can be accessed, managed, and controlled from other computers on the network. There are multiple configuration options available, outlined below, for each family of Network Management Cards or devices that have embedded versions of these products.
- Web/SNMP Card - AP9606
- Network Management Card 1 (NMC1) - AP9617, AP9618, AP9619
- Network Management Card 2 (NMC2) - AP9630/AP9630CH, AP9631/AP9631CH, AP9635/AP9635CH
- Network Management Card 3 (NMC3) - AP9640, AP9641
- All serial numbers
- All firmware revisions (unless otherwise noted)
- Unconfigured Network Management Card-enabled devices
- Network Management Card devices requiring reconfiguration
Resolution
Network Management Card 1:
In regards to Network Management Card 1 (AP9617, AP9618, AP9619) or devices with an embedded Network Management Card 1 (such as a AP78XX or AP79XX Rack PDU, Environmental Monitoring Unit, etc), there are three available options to configure the Network Management Card (NMC) with it's initial settings: the Wizard, terminal emulation (local/direct connection), and Address Resolution Protocol (ARP).
Default boot mode: DHCP/BootP - With DHCP Option 43 Vendor Cookie required to accept DHCP Offer.
By default, all of APC's Network Management Card 1 based devices are configured for a boot mode of DHCP/BOOTP. If using DHCP, a vendor cookie (DHCP Option 43) is required by default. If it is not configured on your DHCP server, the card will not accept an IP address. You can use the methods below to configure/access the card if you do not wish to use DHCP/BOOTP.
Default boot mode: DHCP Only - With DHCP Option 43 Vendor Cookie NOT required to accept DHCP Offer.
By default, all of APC's Network Management Card 2 and 3 based devices (such as an AP8XXX Next Gen Rack PDU (NMC2 only)) with AOS 5.1.1 or higher, are configured for DHCP Only with no vendor cookie required by default. They will obtain an IP address automatically so you may need to refer to your DHCP server to find out what IP address it obtained.
All APC devices have a MAC address that begin with 00 C0 B7 which may help while reviewing your DHCP Client List.
- Device IP Configuration Wizard - (NMC1/NMC2/NMC3)
- Terminal Emulation (Local/Direct connection) - (NMC1/NMC2/NMC3)
- Address Resolution Protocol (ARP) - (NMC1/NMC2/NMC3)
- DHCP Option 12 - (NMC2 v5.1.5 or higher)
- Smart-UPS front panel LCD - (available on supported SMT, SMX, and SRT Models with NMC2/NMC3)
The Device IP Configuration Wizard is a Windows application designed specifically to remotely configure the basic TCP/IP settings of Network Management Cards. The Wizard is included on the CD bundled with the cards, and available to download from the APC website . This utility supports NMC1/NMC2 cards that have firmware version 3.x.x or higher.
Please keep in mind that with certain firmware releases, the NMC can obtain a DHCP address and also prevent the wizard from working correctly. You may want to check your DHCP client list for any MAC addresses beginning with 00 C0 B7, which indicates an APC address. In addition, check the card you are trying to configure. Any card with valid IP settings will have a solid green status LED.
Terminal Emulation is a built-in function on most operating systems (ex: HyperTerminal). Before using any terminal emulation program, any services using the COM ports must be stopped. For example, if you are running a serial version of APC's PowerChute software, the APC UPS service must be stopped prior to running the terminal program. Then, follow these instructions:
NOTE: If you have the scroll lock on, HyperTerminal will not communicate properly with an APC UPS or accessory.
Connect to the UPS/device serial port using the correct APC configuration cable. Part numbers are below for common devices. Please refer to the User Guide if you are not sure or your device is not listed.
!WARNING! - Connecting a non-APC serial cable to your device can cause unwanted, erratic device behavior.
Device | Configuration Cable Part Number |
Most UPS devices with a DB-9 serial port | 940-0024 or 940-1524 (DB-9 to DB-9) |
Rack PDU (AP78XX, AP79XX, AP84XX ** ,AP86XX ** , AP88XX ** , AP89XX ** ) | 940-0144 (RJ-12 to DB-9) |
1st Generation Rack Automatic Transfer Switch (AP7750 only) | 940-1000 (DB-9 to DB-9) |
2nd Generation Rack Automatic Transfer Switch (AP77XX, excludes AP7750) | 940-0144 (RJ-12 to DB-9) |
4th Generation Rack Automatic Transfer Switch (AP44XX ** ) | 940-0144 (RJ-12 to DB-9) |
NetBotz 200/Environmental Monitoring (AP9319, AP9340, AP9320) | 940-0103 (DB-9 to DB-9) |
Rack Air Removal Unit (ACF400, ACF402) | 940-0103 (DB-9 to DB-9) |
** This device is NMC2 based so proceed to NMC2/NMC configuration instructions.
- Apply the port settings to establish the connection.
- Press <Enter> 3-5 times to display the username prompt . *
- Use the default username and password of "apc".
- Choose "Network"
- Choose "TCP/IP"
- Choose "Boot mode"
- Change Boot mode to "Manual"
- Set the system IP, subnet mask, and default gateway.
- Accept changes.
- Press Ctrl-C to return to main menu.
- Log out of console to save changes.
NOTE: * Does not apply to 1st Generation Rack Automatic Transfer Switches for "out of the box" configuration. Refer to User Guide.
Network Management Card 2 (AP9630, AP9631), Network Management Card 3 (AP9640, 19641)and related accessories require different configuration settings in order to be configured locally.
- Within a UPS, the NMC2 devices communicate with the following port settings:
- Apply the port settings to establish the connection.
- Press enter 3-5 times to display the username prompt.
- Use the default username and password of "apc".
- Type help or ? to display all available commands.
- Use the tcpip command to configure manual network settings to assign manual IP settings. The tcpip command automatically changes your boot mode to manual once you submit it. It is necessary to issue a reboot command immediately after assigning your manual settings. Text in italics indicates a variable. For each variable, type a numeric value that has the format xxx.xxx.xxx.xxx.
Example:
apc> tcpip -i 159.216.45.39 -s 255.255.254.0 -g 159.216.45.1
apc> reboot
Use the boot command to change the Network Management Card's boot mode ONLY if you are using DHCP or BootP.
* DHCP/BootP and retry options are only available in NMC2 AOS 5.0.X. It is no longer an option in AOS versions > 5.0.X
For a video representation of NMC2 configuration via terminal emulation, refer to the video below:
- Open a command prompt or terminal window and type the following (replacing <IP address> and <MAC Address> with actual values):
NOTE: On Windows operating systems, you may need to run the command prompt as Administrator in order to use the arp command. To do this, right click on the Command Prompt shortcut and select "Run as Administrator."
- On Mac OS X specifically: sudo<space>arp<space>-s<space><IP address><space><MAC Address>
- Next, use Ping with a size of 113 bytes to assign the IP address defined by the ARP command.
- Windows command format: ping<space><IP address><space>-l<space>113
- The -l option is the letter L but must be lowercase when executing the command, as noted above.
Configuration Option 4 - DHCP Option 12 (NMC2 devices, AOS 5.1.5 or higher only)
Beginning with the AOS 5.1.5 release, the NMC2 has implemented Option 12 (Host Name) as part of the DHCP request. DHCP option 12 uses the devices' host name. As of AOS 5.1.5, the default NMC host name will be apcXXYYZZ, where XXYYZZ represents the last six characters of the MAC Address (enclosed on a slip with the shipped product) of the NMC. It is also available on a sticker on the NMC2 itself.If your network is setup correctly (described below), you will be able to access "unconfigured" / just-out-of-the-box NMCs by referencing the NMC as follows:
1.At a terminal (or DOS) prompt, ping the NMC using ping apcXXYYZZ
Network Setup:
In order for option 12 to work properly, the network segment must be configured with the "Dynamically update DNS A and PTR records for DHCP clients that do not request updates . " (or equivalent) box selected.Configuration Method 5 - via Smart-UPS front panel LCD - (Supported SMT, SMX, and SRT * Models with UPS NMC2/NMC3)
* NOTE: This method can be used to configure the embedded UPS NMC2 or optional secondary NMC2 for SRT models.
Some newer Smart-UPS models provide the capability to configure the Network Management Card 2/3 (NMC2/NMC3) IP address, subnet mask, and gateway using the front panel LCD display menu. Before proceeding, ensure your NMC2/NMC3 is installed in the UPS SmartSlot and is powered, indicated by the status LED on the NMC2/NMC3.
Your UPS display will look similar to one of the following types shown below. Press ESC to bring up the Menu, if not already displayed.
In order to access the NMC2NMC3 configuration functionality through the UPS LCD, the LCD menu must be put into Advanced Mode. This is accomplished by going into the Configuration menu and changing the Menu Type from Standard to Advanced on the UPS's LCD menu. Upon changing this menu setting, you will be able to configure the UPS NMC2/NMC3 by going back into the Configuration menu.
1 minute after settings are applied, and the current IP settings will be displayed under the UPS LCD's About menu.
Все статьи и темы на форумах про выбор АКБ для UPS, чаще всего напоминают темы по выбору моторного масла для авто/мото. Попробуем не уподобляться им, а понять основные принципы выбора аккумуляторов на примере производителя CSB.
Видим у них кучу различных линеек аккумуляторов: GP, GPL, HR, HRL, UPS, TPL.
Начинаем читать: GP, GPL — аккумуляторы универсального применения для малых и средних токов разряда. Рекомендованы для применения в охранных и пожарных системах и ИБП. Нам не подходят. Хотя как раз их чаще всего и покупают, не удосужившись изучить их характеристики.
Серия HR — батареи повышенной энергоемкости и допускающие глубокий разряд (до 11% остаточной емкости), особенно полезны при необходимости больших токов разряда. Отличие батарей «H» — это специальная конструкция решетки, позволяющая повысить выходную мощность на 20%. Они наиболее хорошо подходят к применению в мощных энергоустановках и ИБП.
Буковка «L» в серии, говорит о том, что это батареи увеличенного срока службы (Long Life) в буферном режиме эксплуатации до 10 лет.
Ну и серия UPS — это специально разработанная батарея для эксплуатации в режиме высоких токов при коротком времени разряда.
Для себя я долго выбирал между UPS и HRL, но решил взять HRL. К сожалению – сказать о том, как они себя будут вести в длительной работе, можно будет лет через 5, а некропостерство вроде бы не очень приветствуется. Поэтому будем считать, что это мой личный выбор и навязывать его я не собираюсь. Но вы должны понимать, что необходимо выбирать высокотоковые АКБ, так как они должны уметь отдавать всю накопленную емкость в течение 20-30 минут.
Подбор сборки аккумуляторов
Учитывая, что в сборке используется несколько АКБ, крайне желательно, чтобы они обладали одинаковыми характеристиками. Ибо один некачественный аккумулятор приведет к тому, что вся сборка будет работать совсем не так, как ожидается.
Лет 5 назад, я открыл для себя Ростовскую компанию «Бастион» выпускающую тестеры емкости АКБ под торговой маркой «Скат». Не берусь утверждать про идеальную точность замеров емкости, но для оценки уровня: идеальный-живой-еще послужит-труп, этого тестера более чем достаточно.
В принципе можно замерять емкость банальным зарядом-разрядом с использованием часов, автомобильной лампы на 21W (она дает нагрузку около 1А) и тестера, но это долго и чаще всего лениво.
Ну на крайний случай – просто стараемся ставить свежие аккумуляторы из одной партии и надеяться, что вам повезет.
Электрика – это наука о контактах
Один плохой контакт в сборке из 4 АКБ сведет на нет все ваши потуги, поэтому разбираем сборку крайне осторожно. Обычно в UPS используются разъемы для АКБ с защелками, которые простым выдергиванием так же просто переводятся в состояние убитого.
Поэтому берем маленькую плоскую отвертку, вставляем в разъем как на фото и аккуратно его снимаем, не прилагая особенных усилий.Как подсказал коллега в комментарии — надо просто тянуть за пластиковый кожух, а не за провод. Разъем снимается с легким щелчком.Ну по поводу правильного соединения проводов, я думаю, писать излишне. Если вы полезли внутрь UPS, то явно вам известен принцип последовательного соединения АКБ. А для остальных: бумажка-ручка или смартфон с камерой. По окончании сборки, на всякий случай меряем тестером напряжение на сборке и сравниваем с тем, которое должно быть, исходя из количества АКБ.
«Я все сделал как написано, но оно не помогло»
Тут есть два пути. Путь первый, простой и быстрый – необходимо провести полную калибровку UPS. Для этого нужно нагрузить его более чем на 35% и запустить калибровку, например из программы PowerChute. Это срабатывает примерно в половине случаев. Почему не всегда – тайна покрытая мраком. Поэтому пойдем по длинному, но более надежному пути.
Нам понадобятся: компьютер с COM портом, фирменный кабель (например 940-0024С, программа UpsDiag 2.0 (для безопасности вашего UPS коллега рекомендует лучше использовать apcfix в бесплатном режиме. Ничего не могу сказать по этому поводу кроме того, что категорически не рекомендую в UpsDiag нажимать что-то кроме правки 0 регистра, особенно кнопку автоматического исправления ошибки батарей) и таблица калибровочных значений. Нас интересует значение регистра 0. В таблице указано значение для идеальных, сферических АКБ в вакууме. Любые реальные АКБ дадут после калибровки значение меньше, но не намного.
Для примера возьму реальный UPS SUA1500RMI2U. На момент замены АКБ, UpsDiag показывал значение регистра 0 – 42. То есть АКБ мертвые. Калибровочное значение из таблицы – A1.
Подключаем кабель, запускаем UpsDiag, идем на закладку «Калибровка» и смотрим состояние регистра 0. Записываем на бумажку, щелкаем на него правой клавишей мышки – Изменить. Поднимаем его до значения из таблицы калибровочных значений – A1. Если в таблице нет вашего UPS, то в принципе можно поднять до FF. Ничего страшного от такого не бывает, кроме офигевшего UPS, который покажет, что готов держать нагрузку до второго пришествия.
Затем нам нужно дождаться зарядки АКБ до 100%, нагрузить UPS до 35% или чуть выше и запустить калибровку. По окончании калибровки снова смотрим на значение в 0 регистре и сравниваем его с записанным на бумажке. В вышеописанном SUA1500RMI2U с новыми аккумуляторами HRL1234W значение стало – 98, что в принципе не очень далеко от калибровочного A1.
После всего даем снова зарядиться до 100%, сдергиваем COM кабель, втыкаем обратно сетевую карту и желаем UPSу долгой и счастливой жизни на благо нашей серверной стойки.
Кстати сетевые карты, типа AP9619 на вторичном рынке тоже упали в цене до неприличных значений. Но как их готовить (сброс пароля, обновление прошивки, настройка) – это тема отдельной статьи.
Читайте также: